CPR Certificate

CPR B2ca Test Report

CPR Eca Test Report

CPR Dca Test Report

CPR Test Report From VDE

We Zhejiang Tianjie Industrial Corp.list CPR Products Range here:

 
Series No. Name on Test Report Description of goods Test Report No. Grade Lab.
1 17VATC 360811 - 17VAtC a CLASSE B BOBINE 100M 704151-01/05 E EZU 1014
2 17VATC 360812 - 17VAtC a CLASSE B BOBINE 250M 704151-01/05 E EZU 1014
3 17VATC 360813 - 17VAtC a CLASSE B TOURET 500M 704151-01/05 E EZU 1014
4 17VATC/KOKA 17VATC 198017100 - KOKA 17 VATC 100 Blc 704151-01/06 E EZU 1014
5 17VATC/KOKA 17VATC 198017101 - KOKA 17 VATC 100 Negro 704151-01/06 E EZU 1014
6 17VATC/KOKA 17VATC 198017251 - KOKA 17 VATC 250 Negro 704151-01/06 E EZU 1014
7 TWIN UC23/TWIN RG59 360834 - TWIN UC 23 CABLE TWIN CDT100m (TWIN UC23/TWIN RG59 703845-01/02 E EZU 1014
8 RG6 150037 - RG6 PVC Wh CCS-Al 305m CN 704151-01/08 E EZU 1014
9 RG6 150036 - RG6 PVC Bl CCS-Al 305m reel 704151-01/08 E EZU 1014
10 RG6 150039 - RG6 PVC Wh CCS-Al 305m reel (KOKA6/RG6) 704151-01/08 E EZU 1014
11 KOKA6/RG6 150121 - KOKA 6 PVC Wh Cu-Al, 100m reel 703845-01/01 E EZU 1014
12 UC23/KOKA50/RG59 150151 - KOKA 50 PVC wh, 100m reel 704151-01/07 E EZU 1014
13 KOKA30/RG179 150001 - KOKA 30 PVC Wh100m reel (KOKA30/RG179) 703845-01/03 E EZU 1014
14 RG6/KOKA6 150144 - KOKA 6 PVC Wh CCS 305m reel 704151-01/09 E EZU 1014
15 COAX10/RG6 RG6   PVC   CCS (COAX10/RG6) 704151-01/04 E EZU 1014
16 RG59 RG59  SPE  PVC   CCS  (RG59)  704151-01/01 E EZU 1014
17 VIDEO 0,6/3,7 RG59 SPE PVC BC (VIDEO 0,6/3,7) 704151-01/02 E EZU 1014
18 H-16x2OFC-LSZH 16AWG / 2C Speaker cable 4857-1/2017 B2 ISSeP 2659
19 H-16x2OFC-LSZH 16AWG / 2C Speaker cable 4857-1/2017 B2 ISSeP 2659
20 H-16x4OFC-LSZH-WT 16AWG*4  LSZH (H-16x4OFC-LSZH-WT) 4857-1/2017 B2 ISSeP 2659
21 H-14x2OFC-LSZH 14AWG / 2C Speaker cable 4857-1/2017 B2 ISSeP 2659
22 H-14x2OFC-LSZH 14AWG / 2C Speaker cable 4857-1/2017 B2 ISSeP 2659
23 H-14x4OFC-LSZH 14AWG / 4C Speaker cable 4857-1/2017 B2 ISSeP 2659
24 H-14x4OFC-LSZH 14AWG / 4C Speaker cable 4857-1/2017 B2 ISSeP 2659
25 12X2OFC-LSZH-WT 12AWG*2  LSZH (12X2OFC-LSZH-WT) 4859-1/2017 B2 ISSeP 2659
26 EIB-BUS-2X2-LSZH EIB-BUS-2*2-LSZH (EIB-BUS-2X2-LSZH)  4858-1/2017 B2 ISSeP 2659
27 PROFIBUS L2-BUS Profibus L2-BUS 1x2x0.64,violet
(PROFIBUS L2-BUS VIOLET)
704151-01/03 E EZU 1014
28 PROFIBUS L2-BUS PROFIBUS L2-BUS (BLACK) 704151-01/10 E EZU 1014
29 FIRE ALARM CABLE ALARM KABEL-TALE-2x1 MM2
800605-01/03
C-s1,d2,a1 EZU 1014
30 POWER CABLE TP-90 FR 2x 1.5MM2 SPOTLYSKABEL 20180203 800605-01/02 E EZU 1014
31 2x1.5mm2  LSHF  2x1.5mm2  LSHF    D+s1,d2,a1 EZU 1014
32 RG58 LSZH RG58、SATKK 、SATKKS 236129-TL6-1 D VDE  0366
33 RG59 SPE LSZH RG58、SATKK 、SATKKS 236129-TL6-2 D VDE  0366
34 RG59 FPE LSZH RG59、SAT22 、CT125 、TV125、UV23 、SATKK 、SATKKS 236129-TL6-3 D VDE  0366
35 19VATC LSZH 19VATC、SATKK 、SATKKS 236129-TL6-4 D VDE  0366
36 21VATC LSZH 21VATC、RG6 、SAT18、CT100、TV100、SATKK 、 SATKKS  236129-TL6-5 D VDE  0366
37 17VATC LSZH 17VATC、RG6 、CT100、TV100、SATKK 、SATKKS 236129-TL6-6 D VDE  0366
38 11VATC LSZH 11VATC、RG11 、CT167、TV1167、SATKK 、SATKKS 236129-TL6-7 D VDE  0366
39 UTP CAT5E LSZH Cat 5E UTP 236129-TL6-8 D VDE  0366
40 F/UTP CAT6 LSZH CAT 6A FTP 236129-TL6-9 D VDE  0366
41 UTP CAT6A LSZH CAT 6A UTP LSZH 236129-TL6-10 D VDE  0366
42 FTP CAT5E LSZH CAT 5E FTP LSZH 236129-TL6-11 D VDE  0366
43 F/UTP CAT6 LSZH CAT 6A FTP 236129-TL6-12 D VDE  0366
44 U/FTP CAT6A LSZH U/FTP CAT6A LSZH 236129-TL6-13 D VDE  0366
45 U/FTP CAT7 LSZH  CAT 7  236129-TL6-14 D VDE  0366
46 Telephone cable 2C*1.0mm2 LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
47 Telephone cable 2C*2.5mm2 LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
48 Telephone Cable4C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
49 Telephone Cable 6C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
50 Telephone Cable 8C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
51 Telephone Cable 10C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
52 Telephone Cable 12C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
53 Telephone Cable14C*0.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
54 Telephone Cable 2C*0..6mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
55 Telephone Cable4C*0.6mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
56 Telephone Cable 6C*0.6mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
57 Telephone Cable 8C*0.6mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
58 Telephone Cable 10C*0.6mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
59 Telephone Cable 12C*0.6mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
60 Telephone Cable14C*0.6mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
61 Telephone Cable 3C*0.55mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
62 Telephone Cable 5C*0.55mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
63 Telephone Cable7C*1.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
64 Telephone Cable 2C*1.5mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
65 Telephone Cable 2C*0.5mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
66 Telephone Cable 3C*1.0mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
67 Telephone Cable 3C*1.5mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
68 Telephone Cable 3C*2.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
69 Telephone Cable 4C*1.0mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
70 Telephone Cable 4C*1.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
71 Telephone Cable 4C*2.5mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
72 Telephone Cable 5C*1.5mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
73 Telephone Cable 2C*0.75mm²LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
74 Telephone Cable 3C*0.75mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
75 Telephone Cable4C*0.75mm² LSZH Telephone  cable 236129-TL6-15-16 D VDE  0366
76 RG58 PVC RG58、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
77 RG58 PE RG58、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
78 RG59 SPE PE RG58、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
79 RG59 FPE PVC RG59、SAT22 、CT125 、TV125、UV23 、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
80 19VATC PE 19VATC、SATKK 、SATKKS 236129-TL6-17 F VDE  0366
81 19VATC PVC 19VATC、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
82 21VATC PVC 21VATC、RG6 、SAT18、CT100、TV100、SATKK 、 SATKKS  236129-TL6-17 E VDE  0366
83 21VATC PE 21VATC、RG6 、SAT18、CT100、TV100、SATKK 、 SATKKS  236129-TL6-17 F VDE  0366
84 17VATC PVC 17VATC、RG6 、CT100、TV100、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
85 17VATC PE 17VATC、RG6 、CT100、TV100、SATKK 、SATKKS 236129-TL6-17 F VDE  0366
86 11VATC PE 11VATC、RG11 、CT167、TV1167、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
87 11VATC PVC 11VATC、RG11 、CT167、TV1167、SATKK 、SATKKS 236129-TL6-17 E VDE  0366
88 UTP CAT6E PVC  CAT6E UTP 236129-TL6-17 F VDE  0366
89 UTP CAT6 PVC CAT 6A UTP 236129-TL6-17 E VDE  0366
90 UTP CAT6A PVC CAT 6A UTP 236129-TL6-17 E VDE  0366
91 FTP CAT5E PVC CAT 5E FTP 236129-TL6-17 E VDE  0366
92 FTP CAT6 PVC CAT 6A FTP 236129-TL6-17 E VDE  0366
93 F/UTP CAT6A PVC CAT 6A FTP 236129-TL6-17 E VDE  0366
94 Telephone Cable 2C*0.5mm² PVC Telephone  cable 236129-TL6-17 E VDE  0366
95 Telephone Cable 7C*1.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
96 Telephone Cable4C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
97 Telephone Cable 6C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
98 Telephone Cable 8C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
99 Telephone Cable 10C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
100 Telephone Cable 12C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
101 Telephone Cable14C*0.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
102 Telephone Cable 2C*0..6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
103 Telephone Cable4C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
104 Telephone Cable 6C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
105 Telephone Cable 8C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
106 Telephone Cable 10C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
107 Telephone Cable 12C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
108 Telephone Cable14C*0.6mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
109 Telephone Cable 3C*0.55mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
110 Telephone Cable 5C*0.55mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
111 Telephone Cable 2C*1.0mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
112 Telephone Cable 2C*1.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
113 Telephone Cable 2C*2.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
114 Telephone Cable 3C*1.0mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
115 Telephone Cable 3C*1.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
116 Telephone Cable 3C*2.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
117 Telephone Cable 4C*1.0mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
118 Telephone Cable 4C*1.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
119 Telephone Cable 4C*2.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
120 Telephone Cable 5C*1.5mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
121 Telephone Cable 2C*0.75mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
122 Telephone Cable 3C*0.75mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
123 Telephone Cable4C*0.75mm² PVC Telephone  cable 236129-TL6-18 E VDE  0366
124 U/FTP CAT7 PVC CAT 7 U/FTP 236129-TL6-18 E VDE  0366

 

What is CPR – in general?

Started as a Directive in 1989 (“CPD”) and turned into a Regulation in 2011 (“CPR”) which became applicable from 1st July 2013, the CPR was brought to life by the European Commission to enforce that construction works be designed and executed so as not to endanger the safety of persons, domestic animals or property nor damage the environment.

 

What is the scope of CPR – in general?

Products placed on the market for incorporation in a permanent manner inconstruction works.

What are “construction works”?

Buildings or other civil works including tunnels, bridges, metro stations, etc. (no ships, trains, buses, etc.)

 

What are the goals of CPR?

To define harmonised rules for marketing of construction products within the EU.

To provide a common technical language to assess performance of construction products.

To ensure availability of reliable information to allow comparison of construction products from different manufacturers in different countries.

 

What are the benefits of CPR?

It allows free circulation of construction products in the EU.

It enables national authorities to set performance requirements using a harmonised European standard so that users of construction products can better define their performance demands.

Market surveillance can rely on one common information structure.

 

How does CPR affect cables?

EN 50575 is the harmonised European standard, issued in 2014 and published in the Official Journal of the European Union (OJEU) on 10th July 2015, which specifies requirements for cables used in permanent constructions with regard to their reaction to fire.

 

What is the scope of CPR – for cables?

All cables permanently installed in buildings or other civil works.

Which type of cables?

All cables, including data and telecommunication cables.

All type of conductors, copper and optical fibre.

What is “permanently”?

All horizontal and backbone cables are in scope.

Cable assemblies and patch cords are out of scope.

Are ships, trains, buses, etc. in the scope of CPR?

No, these are not civil works.

 

What does “reaction to fire” mean for cables in CPR?

The fire performance of cables is classified based on a number of criteria:

Flame spread and heat release

Smoke production, acidity and flaming droplets

These criteria and test methods are specified in existing standards IEC/EN 60332-1, IEC/EN 61034-2, IEC/EN 60754-2 and in a new harmonised European standard EN 50399.

How are the cable performance classes defined?

7 Euroclasses for flame spread and heat release: A, B1, B2, C, D, E and F (A being the most severe i.e. non-combustible and F having no criteria specified)

5 classifications for smoke production: s1, s1a, s1b, s2, s3 (s1a being the most severe and s3 no criteria specified or failing any of the other four classifications)

3 classifications for acidity: a1, a2, a3 (a1 being the most severe and a3 no criteria specified or failing any of the other two classifications)

3 classifications for flaming droplets: d0, d1, d2 (d0 being the most severe and d2 no criteria specified or failing any of the other two classifications)

 

How are cables assessed and certified to be CPR compliant?

There are 2 different procedures:

System 1+: to assess Euroclasses B1, B2 and C

A Notified Body issues an Attestation of Conformity after an initial type test and a factory audit including regular production inspections (2x/year) and audit tests on samples taken from the warehouse (1x/year).

System 3: to assess Euroclasses D and E 

Notified Body issues an Attestation of Conformity after an initial type test.

What is a Notified Body?

It is an independent organisation which has been designated by a Member State to carry out conformity assessment according to a directive. It is the obligation of the Member State to notify the European Commission and the other Member States of the designation.

Which are the Notified Bodies for CPR?

For the moment there are none. Test labs which are accredited as Notified Body will be listed on the NANDO Information System of the EC website. (Nando = New Approach Notified and Designated Organisations)

 

Which performance classes need to be used in which buildings/construction works?

The requirements will depend on various parameters such as the type of building, the level of occupation, the difficulty of evacuation, etc.

These requirements are not harmonised and therefore may vary from country to country.

It is the legal obligation of each EU Member State’s government to adopt CPR in national regulation and to guarantee effective surveillance of its market.

 

Who needs to ensure that cables sold in the EU are compliant with CPR?

The one who places the product on the market in the EU is responsible to comply with the CPR obligations. This is either the actual manufacturer or the importer.

 

How can I know whether a cable complies with CPR?

The product needs to have a Declaration of Performance (DoP):

This is a document drawn up by the manufacturer (or importer) in the language(s) required by the EU country where the product is made available and containing defined information such as product identification, its intended use, its declared performance according to CPR and the identification of the Notified Body. The DoP needs to be made publicly available, either on paper or in electronic format. It does not need to accompany the product itself.

The product packaging needs to have defined labelling including CE marking:

Labels on cable drums and boxes need to contain the same data as on the DoP, the reference number of the DoP, the CE mark and the year in which the CE marking was first affixed. The language of the label information can be chosen by the manufacturer (or importer). The cable itself does not need to bear the CE marking nor contain any other of the CPR requirements for labelling.

 

Is the manufacturer solely responsible for CPR compliance?

No, also Distributors, Specifiers and Building Owners bear responsibilities.

Distributors should not resell cables for which there is no DoP and which do not bear the appropriate labelling.

Specifiers must reference appropriate Euroclasses and s/a/d criteria according to national CPR regulations.

Building owners need to ensure that the infrastructure on their building plans is in line with national CPR regulations.

 

When does CPR become mandatory?

As per the publication of EN 50575 in the Official Journal of the European Union (OJEU) on 10th July 2015, the date of application was fixed on 01st December 2015, with a transition period of 12 months. However, due to some minor amendments to EN 50575, the date of application had been postponed to 1st July 2016. Following publication of Amendment 1 to EN 50575 in the OJEU on 10th June 2016  the coexistence period has officially started and will end on 01st July 2017, date when CE marking for CPR becomes mandatory.

 

Can cables already be CE marked for CPR today?

With the publication of EN50575:2014+A1:2016  on 10th June 2016 the coexistence period has officially started, meaning that cables can be CE marked since that date.

 

Are PVC cables doomed to disappear after CPR implementation?

CPR does not forbid the use of PVC cables.

 

What is the CPR requirement for importers (Caleb's customers) in EU and UK?
 

If the importer markets the cable under his own name and brand, he will per definition be the manufacturer (in relation to CE marking and EU directives/regulations) and will therefore also have the same responsibilities as the original manufacturer. Therefore, the importer needs to make sure the products are CPR complaint and with correct CE labeling and also with a DoP Declaration.

 

Do the importers need to get a parallel classification reports/certificates for the products marketed under their own brands?
a. If the cable is type tested under AVCP system 3 (Eca and Dca products), it is no problem that importers do not have the documents under their own name – as long as they can document that the cable has been tested by notified testing laboratory, and have ensured that the manufacturer has an FPC system in accordance with EN 50575 so that the essential characteristics are maintained (constancy of performance).
 
If the importer has multiple suppliers for the given type of cable, he has to add some kind of marking/code to be able to identify the actual manufacturer and to link it to the right classification report. There is no requirement for the syntax/type of code to use – it is up to the importer to decide and to manage (it is under his full responsibility that the applicable assessment procedure has been followed and completed, and that the required technical documentation /technical file is available.
 
b.If the product is to be marketed as Class Cca and B2ca, he must follow AVCP system 1+, and in this case he shall have a product certificate (Certificate of Constancy of Performance) issued by a notified body in his own name.
This CCP further shall include information about the manufacturing plant.

 

What will be the requirement for CE marking/labeling and cable marking?

a.The CE marking shall include information about Class, manufacturer, number of notified body etc. and shall be affixed visibly, legibly and indelibly to the construction product or to a label attached to it. Where this is not possible or not warranted on account of the nature of the product, it shall be affixed to the packaging or to the accompanying documents
 
b.There is no marking requirement for cable. However, it may be good to include the Euroclass for fire reaction for easier reference